Function:
The MTLx575 converts a low-level dc signal from a temperature sensor
mounted in a hazardous area into a 4/20mA current for driving a safe-
area load. Software selectable features include linearisation, ranging,
monitoring, testing and tagging for all thermocouple types and 2-, 3-
or 4-wire RTDs. (For thermocouple applications the HAZ-CJC plug on
terminals 1–3 includes an integral CJC sensor). Configuration is carried
out using a personal computer. A single alarm output is provided and
may be configured for process alarm or to provide notice of early
thermocouple failure.