Function:
The MTLx514 enables a safe–area load to be controlled, through a relay,
by a proximity detector or switch located in a hazardous area. Line faults
are signalled through a separate relay and indicated on the top of the
module. Switches are provided to select phase reversal and to enable
the line fault detection.
LED indicators
Green: power indication
Yellow: channel status, on when output energised
Red: LFD indication, on when line fault detected
Maximum current consumption
25mA at 24V dc
Power dissipation within unit
0.6W at 24V
Safety description
Uo=10.5V Io=14mA Po=37mW Um = 253V rms or dc